Hydraulic Connections - baltur BT 14 G Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HYDRAULIC CONNECTIONS

The pipes that connect the tank tothe burner should be in perfect tight condition; we recommend the use of copper or steel pipes of an
adeguate diameter.Fuel gate valves should be fitted at the end of the rigid pipelines.Fit the filter to the suction pipeline after the gate
valve. Connect the flexible fitting to this, which in turn should be connected to the suction of the burner pump. Connect the flexible fitting
to the return pipe after the gate valve, and then connect it ot the pump return. Filter, flexible pipes and relative connecion nipples are
standard burner accessories. The pump is provided with special connection points for the insertion of control instruments (manometer
and vacuumeter).To ensure reliable and silent operating conditions, the vacuum in suction should not exceed 35 cm Hg equal to 0,46
bar.Maximun suction and return pressure 1,5 bar.
Pump axis
Pump axis
Pump axis
98304_201104
GRAVITY FEED FROM THE BOTTOM OF OIL TANK
1 Oil tank
2 Feed line
3 Filter
4 Burner
5 Degasifier
6 Suction line
7 Return line
8 Fire valve
9 Non return valve
GRAVITY FEED OVER THE TOP OF OIL TANK
1 Oil tank
2 Feed line
3 Filter
4 Burner
6 Suction line
7 Return line
8 Fire valve
9 Non return valve
10 Foot valve
1 Oil tank
3 Filter
4 Burner
6 Suction line
7 Return line
10 Foot valve
N.B. For any missing devices in the pipping, conform to
existing regulations.
H
Measurement between minimum oil level and pump axis
L
Max. legth of suction line, including vertical lifts. For
each bend of valve deduct 0,25 m.
Ø i Internal diameter of pipe
21 / 45
H
Total
meters
meters
Ø i. 10mm
1
30
2
35
3
40
4
45
H
Total
meters
meters
Ø i. 10mm
1
30
2
35
3
40
4
45
Quote P = 3,5 m (max)
SUCTION FEED
H
Total meters
meters
Øi. 10mm
Øi. 12mm
0,5
26
54
1
24
47
1,5
18
38
2
14
30
2,5
10
23
3
6
15
3,5
-
7
E
N
G
L
I
S
H

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bt 14 gw

Tabla de contenido