Descargar Imprimir esta página

LEGRAND Wattstopper LMRC-101 Manual De Uso página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

The LMRC‑101 communicates to all other DLM devices connected to the
DLM Local Network. Connection drawings are for example only. The low
voltage LMRJ cables can connect to any DLM device with an open RJ45
receptacle.
All line voltage wiring is #12 AWG.
Plug n' Go supports the most energy efficient control strategy. For example, if one load,
one switch and one occupancy sensor are connected to the DLM local network, the system
operates the load as Manual‑On, Automatic‑Off.
See DLM device Quick Start Guides to determine how each device affects the PNG
operation of the LMRC‑101.
Load Control Arbitration
To take full advantage of automatic PnG configuration, review these simple rules about load control
arbitration.
After the room controllers are connected to the DLM Local Network and powered up they
automatically negotiate to determine which controller becomes the Master, as well as the load
numbers for each relay on the DLM Local Network.
The Master is the controller with the most load relays. If more than one controller has the most
relays, the one with the highest serial number becomes the Master.
The LMRC‑101 has only one load . In a DLM local network with only LMRC‑101 room controllers,
the LMRC‑101 with the highest serial number is the Master, carrying Load 1 and Load 2. The next
highest serial number would have Load 3 and Load 4, and so forth.
Load Selection Procedure
A configuration button (Config) allows access to our patented Push n' Learn™ technology to change binding relationships between
sensors, switches and loads.
Step 1 Enter Push n' Learn
Press and hold the Config button (on any DLM device) for 3 seconds.
The red LED on the LMRC‑101 begins to blink as does the red LED on ALL other communicating devices connected to the DLM Local
Network.
The red LEDs continue to blink until you exit PnL mode.
All loads in the room turn OFF immediately after entering PnL, then one load will turn ON. This is Load #1, which
is bound to switch button #1 and occupancy sensors as part of the Plug n' Go factory default setting.
All switch buttons and sensors that are bound to this load have their blue LED solid ON.
Step 2 Load selection
Press and release the Config button to step through the loads connected to the DLM Local Network. As each load
turns ON note the devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices
are currently bound to the load that is ON. The blue LED on the room controller or plug load controller connected to the load is also lit.
• To unbind a switch button from a load, press the switch button while its blue LED is ON bright. The blue LED goes dim to indicate
the button no longer controls the load that is currently ON.
• To unbind an occupancy sensor, press the up () or down () adjustment button while its blue LED is ON. The blue LED turns
OFF to indicate the sensor no longer controls the load that is currently ON.
Pressing the switch or up () or down () button again while the load is ON rebinds the load to the button or sensor and the blue LED
illuminates brightly.
PLUG N' GO OPERATION (PNG)
OPTIONAL UNIT ADJUSTMENT - PUSH N' LEARN (PNL)
CONNECTIVITY
Ceiling Mount
Switch
2
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Line/Hot
Black wire
LMRC
101
Room
Controller
Daylight Sensor
J-Box
Load ON/OFF button
Blue LED ON when
load is ON
Serial
Number
0458356155
Master
0458356679
0458356133
Line
Voltage
Neutral
White wire
Load
Red wire
to Load
Room
Load
Controller
Control
LMRC-101
2
0458356155
LMRC-101
1
0458356679
LMRC-101
3
0458356133
Config button &
red LED

Publicidad

loading