Optional Kits - Ferroli FORCE W 60 Instrucciones De Uso

Ocultar thumbs Ver también para FORCE W 60:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FORCE W

Optional kits

The following kits are available on request:
code 042070X0 - HIGH EFFICIENCY CIRCULATING PUMP KIT- 7m. (A - fig. 35)
code 042071X0 - HIGH EFFICIENCY CIRCULATING PUMP KIT- 10m. (A - fig. 35)
code 042072X0 - PLUMBING KIT
The Kit 042072X0 contains:
1
NON-RETURN VALVE - Female 1"1/2 (B - fig. 35)
2
3-Way FAUCET - Female 1"1/2 (C - fig. 35)
It enables shutting off (for maintenance operations) in conformity with ISPESL requirements and can be used as
a local shutoff for the connection of several units in bank. The third way must be connected to an atmospheric
discharge manifold. In this way, with the valve in the "open" position, the boiler exchanger is connected to the de-
livery manifold; and in the "closed" position, through the third way, the exchanger communicates with the atmos-
pheric discharge manifold. This valve therefore also acts as a boiler discharge.
3
FAUCET Male/Female 1"1/2 (D - fig. 35)
In combination with the 3-way valve described above, it enables shutting off (for maintenance operations) in con-
formity with ISPESL requirements and can be used as a local shutoff for the connection of several units in bank.
4
CONNECTION NIPPLE 1"1/2 (E - fig. 35)
In combination with the 3-way valve described above, it enables shutting off (for maintenance operations) in con-
formity with ISPESL requirements and can be used as a local shutoff for the connection of several units in bank.
EN
fig. 35- Boiler with installed kits
cod. 3541Q760 - Rev. 00 - 02/2019
209

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Force w 80Force w 99Force w 120Force w 150Force w

Tabla de contenido