other parameters
Undervoltage
Overvoltage
Voltage imbalance
Reverse power
Overpower
Current imbalance
60 HZ UF_Pickup ~ 65 HZ
Overfrequency
50 HZ UF_Pickup ~ 55 HZ
60 HZ 55 HZ ~ OF_Pickup
Underfrequency
50 HZ 45 HZ ~ OF_Pickup
4.5. FeAtureS oF operAtIon
4.5.1. long delay protection (l)
Adjustments
Adjust of range
Incr.
80 V ~ 0 V_Pickup
1 V
UV_Pickup ~ 980 V
1 V
6% ~ 99%
1%
10 ~ 500 kW
1 kW
500 ~5000 kW
1 kW
6% ~ 99%
1%
1 HZ
1 HZ
1 HZ
1 HZ
Protection against overload, with feature of current
inverse time.
1. Current Ir
a) Adjustment of range in N and A type units:
(0.4~1.0) xIn
- Iu: (0.5-0.6-0.7-0.8-0.9-1.0) xIn
- Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0) xIu
b) Adjustment of range in the P and S type units:
(0.4~1.0) xIn
- Ir: (0.4-0.5-0.6-0.7-0.8-0.9-1.0) xIn
2. Performance time tr
- The performance time is based on current of 6xIr
- Adjustment of range: (0.5-1-2-4-8-12- 16-20-Off)s
3. Start of timing
- It occurs when the current exceeds 1.15xIr
4. The unit performs as per the greatest current
between the phases R, S, T and the neutral N.
time of adjustment
Adjust of
precision
Incr.
range
±5%
±5%
1.2~40s
±2.5% ou
±10%
±10%
0.2~40s
±10%
0.1s
±2.5% ou
±10%
±0.1 HZ
1.2~40s
±0.1 HZ
±0.1 HZ
±0.1 HZ
ABW - Air Circuit Breaker
www.weg.net
precision
±0.1s
31