By this function, a time interval (from 1 minute to 4 hours) can be selected during which the unit can run at
maximum speed. The booster function bypasses any other fan speed control modes. After selecting the
function, a digital chronometer (hours.minutes.seconds) is displayed that is preset on 5 minutes; this value
can be changed by turning the knob clockwise to increase the booster time or counterclockwise to reduce
this time. After selecting the time desired, press the knob to stop the function: the display shows the
remaining time to the end of the procedure; when the 00.00.00 value is reached, the speed returns to be
controlled in the previously selected mode. If the procedure is to be stopped, just repeat the booster
setting operations by selecting 0 minutes.
Post-heating control
The ADVANZ control is able to operate a post-heating system based on a water coil (control of a 3-point
solenoid valve or control of solenoid valve with 0-10 volt signal in modulation) or an electric resistance
(controlled by on-off control or PWM modulation signal). The presence and type of post-heating installed
must be set in the factory. If the post-heating operation is set, the synoptic window changes: an icon that
represents a thermometer with a temperature value on its side is displayed in the bottom right corner and
a box representing post-heating is displayed in the delivery airflow. The desired temperature set point
setting function is accessed by selecting the item in the bottom right corner (Ts).
The Ts value can be increased by turning the knob clockwise or, otherwise, reduced by turning the knob
counterclockwise: once the desired value is reached, confirm your selection by pressing the knob. Ts may
take values between 0 and 30 °C with 1°C steps; when the user selects a Ts value of 0 °C, the control
considers post-heating off and the off writing is displayed on the screen just above the Ts00 value. The
screen indicates the post-heating state:
Post-heating ON
Post-heating OFF