Soler & Palau ADVANZ Instrucciones De Uso página 48

Control y gestión de recuperadores con microprocesador
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ti (in) min
It is the minimum temperature value below which post-heating is triggered by the input probe. If is
expected the use of water-coil as cooling will be displayed other two voices:
Wint Ti in min which is the minimum temperature of Ti in winter season (heating).
Summ Ti in min which is the minimum temperature of Ti in summer season (cooling).
Ti (in) max
It is the maximum temperature value above which post-heating is triggered by the input probe.
Fan exhau.
It is the ratio between the two fan speeds, which has been set by the installer to balance the two air flows
(input and exhaust) according to the system needs. The menu window is accessed through the "close
window" icon:
- turn the knob until the icon is selected. The icon will become bright against a dark background
- press the knob to confirm your selection: the menu window will be displayed
Valve sec
It is only on when modulation-controlled coil- or electric resistance-operated post-heating is present; it
indicates the valve run time.
PIR time m. 010
It is only present when the "PIR" function is on (as set in the factory). It indicates the time (expressed in
minutes) during which fans will run at maximum speed after an external consent received from a motion
detector. After this span of time, the fans will return to the speed set from the control panel, and then to
the minimum speed if no motion is detected in the monitored room.
Boost min 010
It is only present if the "booster" function is on (as set in the factory). It indicates the time (expressed in
minutes) during which fans will run at maximum speed after an external consent.