LERBAKKEN 10, 8410 RØNDE DENMARK
9203Bxxx Installation:
Hazardous area
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt(Po)
Ca(Co) ≥ C
+ Ci
cable
La(Lo) ≥ L
+ Li
cable
Terminal (31,32)
Supply:
Voltage
Power max.
Terminal (33,34)
Status Relay:
Voltage max.
Power max.
Current max.
Revision date:
2015-01-22
44
43
42
41
54
53
52
51
19.2 – 31.2 VDC
3.5 W
Non Hazardous location: Division 2 or Zone 2 installation:
125 VAC / 110 VDC
62.5 VA / 32 W
0.5 AAC / 0.3 ADC
Version Revision
V6R0
9203 - Versión del producto 9203-003
Non Hazardous Area or
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
-20 ≤ Ta ≤ 60ºC
4501
9203
91 92 93 94 95
Power
Rail
Terminal (11,12 and 13,14)
Input:
Voltage
max 28 VDC
Trig: NPN
Low < 2 V, High > 4 V
Trig: PNP
Low < 8 V, High > 10 V
32 VAC / 32VDC
16 VA / 32 W
0.5 AAC / 1 ADC
Prepared by:
PB
9203QF01
34
33
32
31
14
13
12
11
Supply / Input
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253V, max. 400Hz
m
Page:
2/3
33