14.2.2 If password is set

1
2
3
4
5
6
7
8
9
10
* Open is shown briefly in the display

14.3 Functional test

The user is responsible for making a functional test after verification
of safety parameters. The procedure for periodic proof test described in
section 10 shall be used.

15. Fault reaction and restart condition

When the 9203 detects a fault the output will go to Safe State, in which the
safety output will go to "de-energised".
For device faults there are 2 ways of bringing the device out of Safe State.
1. Power cycle the device.
2. Bring the device out of SIL mode (choose "NO" in the menu point "EN.SIL"),
and set it back to SIL mode again (choose "YES" in the menu point "EN.SIL" and
verify the configuration).
9203 Solenoid / Alarm Driver
Action
Press OK
Enter password and press OK
Set (ADV.SET) to Yes and press OK
Step down to (SIL SETUP) and press OK
Set (EN SIL) to YES and press OK
(At this time the device starts operating in
SIL mode with the entered configuration
parameters!)
Press OK to confirme verification of the
OPEN-LOCK in the display
Verify Channel 1 function and press OK
Verify Channel 2 function and press OK
Verify password and press OK
Verify SIL and press OK
Version No. V5R0
Safety Manual
Display shows
PASSW
ADV.SET
DISP SETUP
EN.SIL
Verify OPEN
"briefly"
LOCK*
CH1.FUN
CH2:FUN
PASSW
SIL.OK