Módulo de superficie inalámbrico de 1 elemento para conmutación o regu
lación
Hotel function
Channel settings "switching"
Parameters
Switch-on delay
Switch-off delay
Run-on time
32582722
10864994
On, Off
Basic setting: Off
Setting options, Basic set
ting
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
27.04.2017
If the hotel function is activa-
ted, the system will dim to 20
% brightness when a switch-
off command is made. Switch-
off is only possible with a for-
ced position command.
Note: If the minimum bright-
ness is set to greater than 20
%, then the system dims to
the set minimum brightness
when the hotel function is acti-
vated.
Explanations
The load switches on after a
delay. Repeated switch-on
commands restart the delay ti-
me. If the load has not yet
been switched on due to the
delay when a switch-off com-
mand comes, then the load
will remain off.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
The load switches off after a
delay. Repeated switch-off
commands restart the delay ti-
me. If the load has not yet
been switched off due to the
delay when a switch-on com-
mand comes, then the load
will remain on.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
As soon as a run-on time has
been entered, the actuator will
no longer remain on perma-
nently, but only for the length
of the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is di-
rectly connected to the "Ma-
nual switch-off of run-on time"
parameter.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
11/15