Low Oil Pressure
This shutdown alarm is indicated by Low Oil Pressure on
the digital display. The unit is equipped with an oil pressure
switch that uses normally closed contacts held open by
engine oil pressure during operation. Should oil pressure drop
below the 8 psi range, switch contacts close and the engine
will shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick or contact
your installer or an authorized dealer.
High Coolant Temperature
This shutdown alarm is indicated by High Coolant
Temperature on the digital display. This condition occurs
when the temperature of the coolant exceeds the shutdown
threshold.
To remedy the problem, contact your installer or an
authorized dealer.
External Shutdown 1,2 or 3
This shutdown alarm is indicated by External Shutdown on
the digital display.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Circuit Breaker (GCB) Fail
This shutdown alarm is indicated by GCB Fail on the digital
display. This condition occurs when the generator circuit
breaker trips or becomes non-functional.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Overvoltage
This shutdown alarm is indicated by Generator Overvoltage
on the digital display. This condition occurs when the output
voltage exceeds the preset threshold.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Undervoltage
This shutdown alarm is indicated by Generator Undervoltage
on the digital display. This condition occurs when the output
voltage drops below the preset threshold.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Overfrequency
This shutdown alarm is indicated by Generator Overfrequency
on the digital display. This condition occurs when the
generator frequency is out of limits given by setpoints.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Underfrequency
This shutdown alarm is indicated by Generator
Underfrequency on the digital display. This condition occurs
when the generator frequency is out of limits given by
setpoints.
To remedy the problem, contact your installer or an
authorized dealer.
14
Generator CCW Rotation
This shutdown alarm is indicated by Generator CCW on the
digital display. This condition occurs when the generator
phase is out of sequence.
To remedy the problem, contact your installer or an
authorized dealer.
Start Fail
This shutdown alarm is indicated by Start Fail on the digital
display. This condition occurs when the generator does not
start.
To remedy the problem, contact your installer or an
authorized dealer.
Stop Fail
This shutdown alarm is indicated by Stop Fail on the digital
display. This condition occurs when the generator fails to
stop.
To remedy the problem, contact your installer or an
authorized dealer.
Battery Flat
This shutdown alarm is indicated by Battery Flat on the digital
display. This condition occurs if the controller loses power
during starting sequence due to a bad battery condition. It will
not try to start again until the battery is functioning properly.
To remedy the problem, contact your installer or an
authorized dealer.
Voltage Autodetect
This shutdown alarm is indicated by Voltage Autodetect on
the digital display. This condition occurs if the controller
loses power during starting sequence due to a bad battery
condition. It will not try to start again until the battery is
functioning properly.
To remedy the problem, contact your installer or an
authorized dealer.