Gas Supply Sizing

The vaporization of propane is affected by several
factors: the surface area of the container, the liquid
level of propane, temperature surrounding the
container, and the relative humidity. All of these
factors are specific to a site. Therefore, a degree
of experience and judgement is required to select
the proper propane supply. Although experience
is the best guide, the following recommendations
can be used as a starting point. The table below is
based on experience in northern climates where
cold weather and high humidity are prevalent in the
winter. If more or less favorable conditions prevail
at a specific site, adjustments can be made on the
basis of experience.
Foreman Ductable Dual Fuel Indirect-Fired Heater
Gas Supply Sizing
Owner's Manual • Foreman
If more than one gas supply container is used per
heater, the containers must be connected together by
a manifold to allow vapor withdrawal simultaneously
from multiple containers. The manifold system shall
be in accordance with NFPA 58 or CSA B149.1.