Service Menu
The card is equipped with two Menus: one for configuration and the other for Service.
The configuration Menu is accessed by pressing the DHW buttons together for 10 seconds. 4 parameters modifiable
only from card for security reasons, except one (P02), are available.
Remote
Card
control
NO
P01
29
P02
NO
P03
NO
P04
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
Press the Reset button for 10 seconds to access the card Service Menu. Press the Heating buttons to select "tS", "In",
"Hi" or "rE". tS" means Transparent Parameters Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu
Reset. After selecting the Menu, press the Reset button to access it.
80
Description of Transparent Parameters
Gas type selection
Fan max. frequency in DHW (P02=1)
Fan max. frequency in DHW (P02=2)
Fan max. frequency in DHW (P02=3)
Fan max. frequency in DHW (P02=4)
Fan max. frequency in DHW (P02=5)
Fan max. frequency in DHW (P02=6)
Fan max. frequency in heating (P02=1)
Fan max. frequency in heating (P02=2)
Fan max. frequency in heating (P02=3)
Fan max. frequency in heating (P02=4)
Fan max. frequency in heating (P02=5)
Fan max. frequency in heating (P02=6)
Post-Ventilation
cod. 3540H322 - 09/2008 (Rev. 01)
Reply 51 - 71 - 101
Range
0=Natural
gas,1=LPG
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
0-120 seconds
Default
0=Natural gas
185 Hz
185 Hz
185 Hz
215 Hz
215 Hz
215 Hz
185 Hz
185 Hz
185 Hz
215 Hz
215 Hz
215 Hz
30 seconds