3 Technical description
3.5
3.5.1
28
(1) X22: Test terminal block
Terminal
Function
1
DC connection DC +
2
DC connection DC -
3
AC connection L1
4
AC connection L2
5
AC connection L3
6
AC connection N (not assigned)
7
AC connection PE
8
Auxiliary power supply L
9
Auxiliary power supply N
The test terminal block is available for measurements. If no results are
achieved on the test terminal block, check the fuses for the test
terminal block and measure directly at the connections, if necessary.
(2) X21: Auxiliary power supply connection bar
Terminal
Function
1/2
Auxiliary power supply L
3/4
Auxiliary power supply N
5/6
Auxiliary power supply PE
7/8
Connection for external switch to shut off the auxiliary
power supply (optional)
9/10
Connection (optional): If you want quick deactivation of
the device or if no dynamic grid support (fault ride
through) is required, then assign terminals X21.9/10
(230 V, 10 mA) (see Chapter 3.7.3, page 36).
Front door
ON/OFF switch
The On/Off switch integrated into the front door disconnects the central
inverter in question from the auxiliary power supply (AC grid). In the
process, activation of the central inverter is interrupted. The central
inverter is isolated from the AC grid and the display switches off. The
central inverter no longer participates in communication with other system
components. If you are using the manufacturer's system monitoring, the
Monitoring Display displays a corresponding message.
If the On/Off switch is switched off, the central inverter is no longer
supplying power. For technical reasons, it may be the case that the device
switches off with a time delay (0.2–2 s).
Operating manual
Transformerless central inverter