4 Installation location
Without raised floor
4.2.1
40
1384 mm
Note the following during installation:
Doors must open to 180°.
|
Dimensions of the device.
|
Note the following during installation directly on the floor (without raised
floor):
Space to the side: At least 200 mm
|
Installation can cause an additional workload during a service or
|
maintenance deployment. Access to some components is made easier
through the use of a raised floor. Take this into account when planning
the system and any service contracts.
Space requirement for transport and installation
The transport route must be designed accordingly and must be able to
support the weight of the device, the wheel pressure and the weight of the
crane or industrial truck.
The means of transport must
be designed for the maximum weight of the device and
|
meet the requirements of the installation site.
|
The space requirement for installation depends on local and project-
specific factors. If you are transporting the device with the crane, note the
following:
Space requirement > half the support width of the crane + 1 m safety
|
space to the pit + 1 m working area around the pit + half the width of
the device. Pit means the gap in the raised floor or the recess in the
floor.
Operating manual
1600 mm
Transformerless central inverter
1781 mm