Wilo TOP-Z Serie Instrucciones De Instalación Y Funcionamiento página 41

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 95
Pump with terminal
box type
1~230 V
1/2
(P
max ≤ 205 W)
1
3/4
(320 W ≤ P
1
≤ 345 W)
5
(320 W ≤ P
1
≤ 345 W)
Pump with terminal
box type
3~400 V
6
(P
max ≤ 215 W)
1
7
(305 W ≤ P
1
≤ 1445 W)
• The setting of any thermal tripping that is fitted must correspond to the maxi-
mum current (see rating plate) of the speed stage at which the pump is being
operated.
Motor protection tripping devices
If Wilo tripping units SK 602(N)/SK 622(N) are present in existing systems,
pumps with full motor protection (WSK) can be connected to them. Establish
the mains connection and the tripping unit connection (observe rating plate
data) in accordance with the circuit diagram in fig. 7a:
1~230 V: 320 W ≤ P
Installation and operating instructions Wilo-TOP-Z
Tripping
Internal disconnection
of motor voltage
Thermal winding con-
tact and external trip-
max
ping unit (SK602 (N) /
SK622(N) or other
switching/control
device)
All-pole deactivation
by the integrated trip
max
electronics
Tripping
Internal disconnection
of a motor phase
All-pole deactivation
by the integrated trip
max
electronics
max ≤ 345 W, with thermal winding contact
1
SSM
-
-
Tripping of the SSM
is performed parallel
to deactivation of
the integrated trip
electronics
SSM
-
Tripping of the SSM
is performed parallel
to deactivation of
the integrated trip
electronics
Fault
acknowledgement
Automatically, after
the motor has cooled
down
After cooling of the
motor by SK602/
SK622: manually at the
tripping unit
by SK602N/SK622N:
automatically
Manually at the pump,
after the motor has
cooled down
Fault
acknowledgement
• Switch off mains
voltage
• Allow motor to cool
down
• Switch on mains
voltage
Manually at the pump,
after the motor has
cooled down
English
37