2 Wire Start /Stop
XDI
Terminal Block
STOP
START
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
DI6
6
XD24
Terminal Block
1
DIIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
J6
Ground selection
switch
Note: Set Start/Stop to 2 Wire DI1
Be Sure J6 is in the ON position (Default)
OFF
ON
Dual Start/Stop Locations
This configuration enables the user to toggle between two different control locations.
An example of this would be if the customer has one Start/Stop switch located at the
pump (REM) and the another in the control room (LOC). When digital input 3 is
activated the start/stop source is the pump (REM).
L
OCALIZED / REMOTE SELECTOR SWITCH
DI3 OPEN = LOCAL
DI3 CLOSED = REMOTE
!! NOTE !!
The DII L is a drive permissive and must be
closed (24Vdc) for the drive to operate. If
your application does not require a Drive
Permissive, DIIL may be bypassed by
jumping DIIL to XD24 connections #2 or #4
Note:
Set Start/Stop 12.01 to 2W DI 1- 2WDI5
209 PS220
Start / Stop Options - Single External Control Locations
OFF
HAND
!! NOTE !!
The DII L is a drive permissive and must be
closed (24Vdc) for the drive to operate. If
your application does not require a Drive
Permissive, DIIL may be bypassed by
jumping DIIL to XD24 connections #2 or #4
Start / Stop Options - Dual External Control Locations
XDI
Terminal Block
OFF
AUTO
HAND
X00
1
DI1
00X
2
DI2
LOCAL
REMOTE
3
DI3
4
DI4
STOP
START
5
DI5
DI6
6
XD24
Terminal Block
1
DIIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
Ground selection
J6
switch
H-O-A
XDI
AUTO
Terminal Block
00X
1
DI1
X00
2
DI2
3
DI3
4
DI4
5
DI5
DI6
6
XD24
Terminal Block
1
DIIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
J6
J6
Ground selection
Ground selection
The DII L is a drive permissive and must be
switch
switch
closed (24Vdc) for the drive to operate. If
your application does not require a Drive
Permissive, DIIL may be bypassed by
jumping DIIL to XD24 connections #2 or #4
Note: Set Start/Stop to HOA
Example : Speed Override when H-O-A switch in Hand Mode
This configuration enables the user to toggle between two different control locations.
An example of this would be if the customer has one hand-off-Auto switch in the field
(by the pump) and requires that in hand mode the pump be run from the local station
and in Auto mode the pump be controlled by a remote location.
!! NOTE !!
The DII L is a drive permissive and must be
START/STOP
closed (24Vdc) for the drive to operate. If
from Control Room
your application does not require a Drive
Permissive, DIIL may be bypassed by
jumping DIIL to XD24 connections #2 or #4
Note:
Set start/stop to HOA DI1,2-D15
3 Wire Start /Stop
[Momentary Push Buttons]
XDI
Terminal Block
START
1
DI1
2
DI2
STOP
3
DI3
4
DI4
5
DI5
DI6
6
XD24
Terminal Block
DIIL
1
2
+24VD
3
DICOM
4
+24VD
!! NOTE !!
5
DIOGND
J6
Ground selection
switch
Note: Set Start/Stop to 3W DI1P, D12P
XDI
Terminal Block
OFF
HAND
AUTO
00X
1
DI1
X00
2
DI2
LOCAL
REMOTE
3
DI3
4
DI4
STOP
START
5
DI5
6
DI6
XD24
Terminal Block
1
DIIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
Ground selection
J6
switch