Multi-Circuit Condenser - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

PARAMETER
NAME
READ ONLY
Liquid cooler circuits:
0 = 1 circuit, 1 probe
1 = 1 circuit, average of 2 probes
PG04
(Vshape dry cooler with Spray
Evolution or EMERITUS®)
2 = 2 circuits with independent set-
point (LT + HT)
Adjustment Priority for Liquid
Cooler 2 Circuits:
PG06
0 = Worse case
1 = circuit 1 priority
2 = circuit 2 priority
PR20
Liquid cooler circuit 2 set-point
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PG04
Liquid cooler number of
0x0C0E
3087
circuits
PG06
Adjustment Priority for
0x0C17
3096
Liquid Cooler 2 circuits
PR20
Liquid cooler circuit 2 set-
0x0C0C
3085
point
6.3
In the case of a two-circuit condenser, the setting will take as the reference the highest condensing pressure, or the
lower evaporation pressure, giving priority to the circuit requiring more resources. Both circuits have the same
reference set-point (PR02). In case of failure of one of the two pressure probes, the adjustment is made only based on
the circuit with the active probe, and a failed probe warning is returned. Parameter PG03 defines the number of
condenser circuits, and enables the input of the second AI2 pressure probe.
PARAMETER
NAME
PG03
Number of condenser circuits
* For dry condensers, the maximum number of circuits possible is 3
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PG03
Number of condenser
0x0834
2101
circuits
LU1W - User Manual
DESCRIPTION
Data Type and Notes
0 = 1 circuit, 1 probe
1 = 1 circuit, average of 2
probes (Vshape dry cooler
with Spray Evolution or
EMERITUS®)
2 = 2 circuits with
independent set-point
- unsigned short int
0 = worse case
1 = circuit 1 priority
2 = circuit 2 priority
- unsigned short int
[unit of measure as set by
PH02, default °C]
- short int

Multi-circuit condenser

DESCRIPTION
Data Type and Notes
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
0
0
0
0
45.0
PR22
Default
value
0
0
45.0
DEFAULT
MIN
VALUE
VALUE
2
1
Default
value
1
62
MAX
UM
VALUE
-
2
CONFIGURATION
-
2
CONFIGURATION
PR21
°C
Decimal
Min
Max
positions
0
2
0
2
PR22
PR21
MAX
UM
VALUE
-
2*
CONFIGURATION
Decimal
min
Max
positions
1
2
REV.1.1 – 07/11/2017 - ENG
MENU
ADVANCED →
ADVANCED →
ADVANCED →
REGULATION
MODBUS
Register
Type
0
input
0
holding
0.0
holding
MENU
ADVANCED →
MODBUS
Register
Type
0
holding