8.1
The Silent Mode function, when activated, limits the maximum fan speed in order to reduce the sound output of the
exchanger. This mode can be set via parameter PF30. The maximum fan speed in Silent Mode corresponds to
parameter PF33.
The Silent Mode can be activated via DI4 digital input, according to time zone, or both modes (only one of the two
activation conditions need be true for the silent mode to be active). In the case of time zone activation, it is sufficient
to set the start-up time parameter (PF31) and end time (PF32). For digital input activation, the polarity of the contact
can be changed by parameter PH39 (N.O. → contact open = inactive, contact closed = active silent mode).
PARAMETER
NAME
Silent Mode Activation and
Frequency:
0: No (Disabled)
PF30
1: DI
2: Time Bands
3: DI + Time Bands
PF31
Silent Mode Start Time
PF32
Silent Mode End Time
Maximum fan speed in Silent
PF33
Mode
Logic DI4 silent mode activation
PH39
N.O. = normally open contact
N.C. = normally closed contact
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PF30
silent mode activation and
0x07BE
1983
frequency
PF31 (Low)
0x07BF
1984
silent mode start time
0x07C0
1985
PF31 (High)
PF32 (Low)
0x07C1
1986
silent mode end time
0x07C2
1987
PF32 (High)
PF33
maximum fan speed in
0x07C3
1988
silent mode
ui_silentModeON
silent mode activation
0x0507
1288
status
LU1W - User Manual
8 ADDITIONAL FUNCTIONS
Silent Mode
DESCRIPTION
Data Type and Notes
0 = No, 1 = DI, 2 = Time
Bands, 3 = DI + Time Bands
- unsigned short int
number of seconds from
midnight
- long int divided into 2
word 16 bit
number of seconds from
midnight
- long int divided into 2
word 16 bit
[%]
- unsigned short int
0 = OFF, 1 = ON
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
DI + Time
No
OF
20:00:00
17:00:00
7:00:00
0:00:00
60.00
0.00
N.O.
N.O.
Default
value
0
20:00:00
7:00:00
60.00
-
73
MAX
UM
VALUE
-
Bands
hh: mm: ss
23:59:59
12:00:00
hh: mm: ss
100.00
%
-
N.C.
Decimal
min
Max
positions
0
3
17:00:00
23:59:59
0:00:00
12:00:00
0.00
100.00
0
1
REV.1.1 – 07/11/2017 - ENG
MENU
USER →
SILENT MODE
USER →
SILENT MODE
USER →
SILENT MODE
USER →
SILENT MODE
ADVANCED →
VARIOUS
MODBUS
Register
Type
0
holding
0
holding
0
holding
0.00
holding
0
input