8.2
In case of prolonged fan inactivity, this self-maintenance function is activated. To activate the antilock, the unit must
be switched on.
If the fans remain OFF for duration PL02 since the last activation, all the system fans are activated at the same time for
duration PL03. For the duration of the starting up process, the fans rotate at the speed indicated by parameter PL01.
Antilock rotation is also activated by the antifreeze function in the event of fan inactivity if the outdoor temperature
remains below temperature threshold parameter PL04 for a duration equal to parameter PL05.
To deactivate the function, simply set parameter PL01 to 0%.
PARAMETER
DESCRIPTION
NAME
PL01
Fan Speed in antilock mode
Fan inactivity time for antilock
PL02
activation
Activation time of fans in
PL03
antilock mode
Ambient temperature
PL04
threshold for antilock
activation
Standby time ambient temp.
PL05
below threshold for antilock
activation
*corresponding to 14 days; ** corresponding to 12 hours
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PL01
0x07F1
2034
Fan speed in antilock mode
PL02
Fan inactivity time for
0x07F2
2035
activating antilock
PL03
Activation time of fans in
0x07F3
2036
antilock mode
PL04
Ambient temperature
threshold for antilock
0x07F4
2037
activation
PL05
Standby time ambient
temp. below threshold for
0x07F5
2038
antilock activation
ui_ALockOn
0x0508
1289
Antilock activation state
LU1W - User Manual

Fan Antilock

DEFAULT
VALUE
70.00
20155*
5
-2.0
720**
Data Type and Notes
[%]
- unsigned short int
[min]
- unsigned short int
[min]
- unsigned short int
[unit of measure as set by
PH02, default °C]
- short int
[min]
- unsigned short int
0 = OFF, 1 = ON
- unsigned short int
MIN
MAX
UM
VALUE
VALUE
0.00
100.00
0
61000
0
20000
-30.0
20.0
0
20000
Default
Min
value
70.00
0.00
20155
0
5
0
-2.0
-30.0
720
0
0
0
74
PARAMETER
MENU
NAME
ADVANCED →
%
ANTILOCK
ADVANCED →
min
ANTILOCK
ADVANCED →
min
ANTILOCK
ADVANCED →
°C
ANTILOCK
ADVANCED →
min
ANTILOCK
MODBUS
Decimal
Max
Register
positions
Type
100.00
0.00
holding
61000
0
holding
20000
0
holding
68.0
0.0
holding
20000
0
holding
1
0
input