Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PC02 (Low)
0x07E5
2022
Cleaning Start Time
0x07E6
2023
PC02 (High)
PC03
0x07E7
2024
Cleaning Day
PC04
Fan speed in cleaning
0x07E8
2025
mode
PC05
0x07E9
2026
Cleaning cycle time
vCeaningON
0x0509
1290
Cleaning activation status
8.4
Washing is done by spraying wet on the coil with idle fans. The washing function can be activated via parameter PC10.
It can be set daily (with washing start time parameter PC11) or weekly (with washing day parameter PC12 and
washing start time parameter PC11). The function only starts when the unit is on.
The sequence will be as follows:
Activation time arrives, the instrument closes the warning relay to the master supervisor (DO10)
After a set time (parameter PC13) the fans are switched off
After a settable time has elapsed (parameter PC14), the sprayers are activated
Wash has a settable duration (parameter PC15)
At end of washing, after a settable time (parameter PC13), the warning signal is switched off to the master
and the fans are unlocked and will follow their normal adjustment.
By parameter PH40, you can set the inbound function to wait for a master digital supervisor (DI6) to confirm. In this
case, instead of waiting for a fixed time before switching the fans on and off, the washing cycle waits for the signal
from the master controller.
To improve washing efficiency, it is recommended to perform it with a cold machine, i.e. without circulation of the
fluid inside the exchanger.
You can also start the washing cycle manually from the ADVANCED → MANUAL menu. On the CLEANING screen, move
the cursor over the UP and DOWN keys to Run, in the Coil window, then press ENTER.
LU1W - User Manual
Data Type and Notes
number of seconds from
midnight
- long int divided into 2
word 16 bit
0 = Sunday
1 = Monday
---
6 = Saturday
- unsigned short int
[%]
- unsigned short int
[sec]
- unsigned short int
0 = OFF, 1 = ON
- unsigned short int

Coil Wash

Default
Min
value
23:00:00
0:00:00
0
0
100.00
0.00
60
1
0
0
76
MODBUS
Decimal
Max
Register
positions
Type
23:59:59
0
holding
6
0
holding
100.00
0.00
holding
9999
0
holding
1
0
input
REV.1.1 – 07/11/2017 - ENG

Publicidad

Tabla de contenido
loading

Tabla de contenido