MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PH40
Enable DI9 start coil wash
0x0823
2084
command
PH41
Logic DI9 start coil wash
0x0824
2085
command
ui_WashingON
0x05C2
1475
Coil wash activation status
8.5
When the machine is installed in particularly cold climates, the operation of the controller or LCD display may be
impaired. To ensure that this does not happen, a heating resistor housed inside the electrical cabinet is controlled
through a digital output DO1.
The heater is activated when the indoor temperature of the electrical panel falls below the PE31 activation threshold
and is deactivated when it rises above this temperature + PE32 return differential. Activation of the resistor can be
disabled by parameter PE30.
Attention: if the user disables this function, said user is responsible for any failures or breaks caused by the low
temperature.
PARAMETER
NAME
PE30
Enables frost resistance
Electrical panel temp. threshold
PE31
for frost resistance activation
Electrical panel differential temp.
PE32
for frost resistance deactivation
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PE30
0x07E1
2018
Enables frost resistance
PE31
Electrical panel temp.
threshold for frost
0x07E2
2019
resistance activation
PE32
Electrical panel differential
temp. for frost resistance
0x07E3
2020
deactivation
LU1W - User Manual
Data Type and Notes
0 = disabled,
1 = enabled
- unsigned short int
0 = N.O. contact,
1 = N.C. contact
- unsigned short int
0 = OFF, 1 = ON
- unsigned short int

Frost protection

DESCRIPTION
Data Type and Notes
0 = No
1 = Yes
- unsigned short int
[unit of measure as set by
PH02, default °C]
- short int
[unit of measure as set by
PH02, default °C]
- unsigned short int
Default
value
0
0
0
DEFAULT
MIN
VALUE
VALUE
Yes
No
10.0
-30.0
2.0
0.0
Default
value
1
10.0
2.0
78
Decimal
Min
Max
positions
0
1
0
1
0
1
MAX
UM
VALUE
Yes
-
°C
20.0
°C
10.0
Decimal
min
Max
positions
0
1
-30.0
68.0
0.0
72.0
REV.1.1 – 07/11/2017 - ENG
MODBUS
Register
Type
0
holding
0
Holding
0
input
MENU
ADVANCED →
T. OUTDOOR
ADVANCED →
T. OUTDOOR
ADVANCED →
T. OUTDOOR
MODBUS
Register
Type
0
holding
0.0
holding
0.0
holding

Publicidad