** Packed Alarm Organization:
PackedAlarm1:
BIT 0
BIT 1
BIT 2
BIT 3
ES01
ES02
ES03
ES04
PackedAlarm2:
BIT 0
BIT 1
BIT 2
BIT 3
APH1
AF01
AF02
AF03
PackedAlarm3:
BIT 0
BIT 1
BIT 2
BIT 3
AF16
AF17
AF18
AF19

13.2 Alarm Management Parameters

With parameter PA00, alarms manual reset can be set after the unit is switched off and restarted.
Parameter PA01 defines the delay time with which a probe error is reported due to an anomaly on the probe itself.
Parameter PF23 represents the speed % at which the ventilation is forced due to loss of the adjustment variable
reference (probe alarm). In case of multi-circuit exchangers, this condition only occurs if the failure occurs on all
adjustment probes relative to the controlled circuits.
With parameter PE14, you can enable the use of wet resources even after an anomaly of the ambient temperature
probe. In this case, wet resources are enabled only based on the request in the adjustment mode.
Attention: Enabling wet resources supply in the absence of the ambient temperature probe may result in
overexploitation of the adiabatic sprayers and panels, which in turn reduces the useful life of the adiabatic panels and
inhibits the blocking risk of overtime for spray (which may not be available at a time of real need of the resource).
Also, in the absence of the ambient temperature probe, the antifreeze functions are inhibited with consequent ice
risk.
PARAMETER
NAME
PA00
Reset alarms at power on
PA01
Probe error report delay
PF23
Fan speed in probe error
Enable wet resource adjustment
PE14
with outdoor temp. probe error
LU1W - User Manual
BIT 4
BIT 5
BIT 6
ES05
ES06
ES07
BIT 4
BIT 5
BIT 6
AF04
AF05
AF06
BIT 4
BIT 5
BIT 6
AF20
AF21
AF22
DESCRIPTION
BIT 7
BIT 8
BIT 9
BIT 10
ES08
ES09
ES10
ES11
BIT 7
BIT 8
BIT 9
BIT 10
AF07
AF08
AF09
AF10
BIT 7
BIT 8
BIT 9
BIT 10
AL04
AL05
AL06
AL07
DEFAULT
MIN
VALUE
VALUE
Yes
No
8
1
100.00
0.00
No
No
103
BIT 11
BIT 12
BIT 13
ERTC
AL01
AL02
BIT 11
BIT 12
BIT 13
AF11
AF12
AF13
BIT 11
BIT 12
BIT 13
AL08
AL09
AL10
MAX
UM
VALUE
Yes
-
Sec
255
%
100.00
Yes
-
REV.1.1 – 07/11/2017 - ENG
BIT 14
BIT 15
AL03
ASH1
BIT 14
BIT 15
AF14
AF15
BIT 14
BIT 15
AL11
ASH2
MENU
ADVANCED →
SAFETIES
ADVANCED →
SAFETIES
ADVANCED →
VENTILATION
ADVANCED →
T. OUTDOOR