Nicheless Underwater LED Lights | Owner's Manual
NOTE: Service
Loop not applicable
for Junction Box
Installations.
Figure 3.
Standard installation with 1.5" pool wall fitting
Section 3.
Jandy
Pro Series Nicheless LED Lights
®
NOTE: Always consider the cable length when calculating the input
voltage at the transformer. The maximum run of service between
transformer and lights should not exceed 150ft. in length, inclusive
of the use of J Box or not.
To the extent allowed by local installation codes in effect in the installation
jurisdiction and capacity of the electrical equipment, multiple Jandy Pro
Series lights may be controlled with a single switch and transformer so
their colors may be synchronized.
IMPORTANT NOTE:
circuit or switch for synchronization to occur. The use of Solid Core over
Stranded wire and terminating Bus Bars is strongly recomended.
3.1
Wiring to an AquaLink
The Jandy Pro Series Nicheless LED Lights can be controlled by an
AquaLink controller. Connect the transformer powering the lights to one
of the auxiliary relays in the AquaLink.
Refer to Figure 4 to connect the Jandy Pro Series Nicheless LED Lights to
the Power Center.
12VAC Pool Transformer,
see table 3.2 for more details
Wiring Options for Controlling
All fixtures must be tied into the same transformer,
ENGLISH
Vertical Installation for
Benches, Swimouts and
Fountains
Controller
®
Page 7