3. Electrical work
3.1.4. Connecting external input
Demand control is available by external input.
It is possible to set the outdoor unit's power consumption by setting the switch of the interface controller.
Switch1, Switch 6 : Input selection of inverter capacity setting
Input
SW 1-1 SW 1-2 SW 1-3 SW 6-1 SW 6-2
REMOTE SWITCH
OFF
OFF
Type A (4bit-8 setting)
REMOTE SWITCH
ON
OFF
Type B (1bit-1 setting)
4-20mA
ON
ON
1-5V
ON
ON
0-10V
OFF
OFF
0-10kΩ
ON
OFF
No input (AUTO mode)
OFF
ON
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
TB142
TB142
TB142
10-11
10-12
10-13
(COM-IN5)
(COM-IN6)
(COM-IN7)
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
TB62
Photo.3-5
TB142
• External function setting
This function is setting operation mode or stopping compressor, by the external signal.
TB142
Item
1-2 (IN1)
Forced Comp. OFF
3-4 (IN2)Item Fixed operation mode Cooling
Cable length : Maximum 10m
Remote switch : Minimum applicableload DC12V, 1mA
Caution:
The external input signals are separated by basic insulation from power supply for the unit.
The external input signals should be separated by supplementary insulation from where user may touch in case that it is installed where
user may touch.
Connect the terminals by using the ring terminals and also insulate the cables of adjoining terminals when wiring to terminal block.
6
Step for capacity setting
OFF
OFF
OFF
OFF/Step1/Step2/.../Step7/Auto step
OFF
OFF
OFF
OFF/Step1/Step4/Step7/Auto step
OFF
ON
ON
OFF/Step1/Step2/.../Step7
OFF
OFF
ON
OFF/Step1/Step2/.../Step7
ON
OFF
OFF
OFF/Step1/Step2/.../Step7
ON
OFF
OFF
OFF/Step1/Step2/.../Step7/Auto step
ON
OFF
OFF
Only Auto step mode
TB142
Step for capacity setting
10-14
(COM-IN8)
TypeA
OFF
[OFF]
OFF
0%
OFF
[ON]
Step1
10%
OFF
Step2
20%
OFF
Step3
30%
OFF
Step4
50%
OFF
Step5
70%
OFF
Step6
80%
OFF
Step7
100%
ON
Auto step
At site
I/F
10
{
11
4 bit 8 switch
12
OFF∼AUTO step
13
14
TB142
OFF
ON
Remark
Normal
Forced Comp. OFF
Heating
Available when SW2-1 and SW2-2
are ON
Remark
TypeB
[OFF]
OFF
0%
OFF
[ON]
Step1
10%
Step4
50%
Fixed capacity
(Hz fixed)
Step7
100%
mode
Auto step mode
Auto step
At site
I/F
10
Step1
11
12
Step4
13
Step7
14
AUTO step
TB142
Demand control is available by connecting remote switches with terminal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch)
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load DC12V, 1mA
• 4-20mA / 1-5V / 0-10V / 0-10kΩ
1Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 3 and 4 on the terminal block (TB62).
No. 3 on the terminal block(TB62) : Plus side
No. 4 on the terminal block(TB62) : Minus side (Reference side)
2Use adjustable resistor (0-10kΩ)
Connect the transmission cables to No. 1 and 2 on the terminal block (TB62).
Adjustable
resistor
4-20mA
(0-10kΩ)
0~100Ω
4~5mA
0~1.25V
510Ω
7mA
1.75V
1kΩ
9mA
2.25V
2kΩ
11mA
2.75V
3.3kΩ
13mA
3.25V
4.3kΩ
15mA
3.75V
5.6kΩ
17mA
4.25V
7.5kΩ
19~20mA
4.75~5V
10kΩ
OPEN(12kΩ~)
*The value of the above-mentioned table becomes the center of the input value.
Cable length : Maximum 10m
Wired remote controller
Step for
1-5V
0-10V
capacity
setting
0~0.63V
OFF
0% Stop
1.88V
Step1
10%
3.13V
Step2
20%
4.38V
Step3
30%
5.63V
Step4
50%
6.88V
Step5
70%
8.13V
Step6
80%
9.38~10V
Step7 100%
Auto step
OFF
0% Stop
At site
I/F
1
I/F
(
0-10 kΩ
2
3
+
(
4-20mA/1-5V/0-10V
4
At site
5
(
6
(For maintenance)
TB62
Remark
Fixed
capacity
(Hz fixed)
mode
Auto step
mode
TB142
1
2
3 4

Publicidad