Pipe Size (mm/in)
6.35 (1/4)
9.53 (3/8)
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
Ø Tube, D
Inch
mm
1/4"
6.35
3/8"
9.52
1/2"
12.70
5/8"
15.88
3/4"
19.05
Electrical Wiring Connection For CE Series 10~25C
Indoor Unit
Outdoor Unit
Voltage range (2)
Recommended fuse (1)
Power Supply Cable size
Number of conductors (1)
Interconnection Cable size
Number of conductors (1)
CE 10~25C
COMP
L
Terminal Strip
Indoor Unit
N
Electrical Wiring Connection For CE Series 30~35C
Indoor Unit
Outdoor Unit
Voltage range (2)
Recommended fuse (1)
Power Supply Cable size
Number of conductors (1)
Interconnection Cable size
Number of conductors (1)
IMPORTANT: (1) These values are for information only, they should be checked and selected to comply with the local and/
or national codes and regulations. They are also subjected to the type of installation and size of conductors
used.
(2) The appropriate voltage range should be checked with label data on the unit. ETL listed unit is only
applicable to 60Hz power supply only.
Torque (Nm)
18
42
55
65
78
A (mm)
Imperial
Rigid
1.3
0.7
1.6
1.0
1.9
1.3
2.2
1.7
2.5
2.0
ELECTRICAL WIRING CONNECTION
CE 10C
SL 10B
220V – 240V/1Ph/50Hz + ! or 208V - 230V/1Ph/60Hz+!
A
10
2
mm
1.5
3
2
mm
1.5
3
Interconnection Cable
Power Supply
Cable
A
mm
2
2
mm
Flare Joint
Indoor Piping
Spanar
CE 15C
CE 18C
SL 15B
SL 18B
10
16
1.5
2.5
3
3
1.5
2.5
3
3
COMP
N
The electrical power must be provided with
!
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3mm.
CE 30C
SL 30C
220V – 240V/1Ph/50Hz + ! or 208V - 230V/1Ph/60Hz+!
25
4.0
3
4.0
4
1-6
Flared Tube
Flare Nut
Torque Wrench
CE 20C
CE 25C
SL 20B
SL 25B
16
20
2.5
2.5
3
3
2.5
2.5
3
3
Terminal Strip
Outdoor Unit
CE 35C
SL 35C
25
4.0
3
4.0
4