0: Jog run
Upon receiving jog run command (for instance, press
the key on keypad)
during waiting state, the inverter run at jog frequency (see function code
F01.25~F01.29).
1: Closed-loop run
The inverter will come into closed-loop run mode when closed –loop run
control effective parameter is set (F11.00=1or F12.00≥1). Namely carry on
PID adjustment to specifi ed value and feedback value (proportion integral
differential calculation, see F11 group function code) and PID adjuster output
is inverter output frequency. Can make closed-loop run mode ineffective and
switch to lower level run mode by multi-function terminal (function 31).
2: PLC run
The inverter will enter into PLC run mode and run according to run mode
preset (see F10 group function code description) through setting PLC function
effective parameter (F10.00 last bit≠0). Can make PLC run mode ineffective
and switch to lower level run mode by multi-function terminal (function 36).
3: multi-section speed run
By nonzero combination of multi-function terminal (5,6,7,8, function), choose
multi-section frequency 1~15 (F10.31~F10.45) to run at multi-section speed.
4: swing frequency run
The inverter will enter into swing frequency run mode when swing frequency
function effective parameter(F13.00=1) is set. Set relevant swing frequency
run special parameter according to textile swing frequency craft to realize
swing frequency run.
5: common run
Common open loop run mode of general inverter.
In above 6 kinds of run mode except "jog run" the inverter can run according to
kinds of frequency setting method.
156