Descargar Imprimir esta página

Fronius IG-TL Serie Manual De Instrucciones página 61

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 223
0x9F - Set power
reduction and
reactive power
Using the '0x9F - Set power reduction and reactive power' command, the respective
inverter can be set to a remote control mode to activate effective power reduction and/or
a reactive power specification from a 3rd party device.
-
-
Important To maintain the remote control mode for a command regarding reactive
power for longer periods of time, the respective command should be sent cyclically in
intervals of at most 60 seconds.
Possible values in the 'Remote Ctrl CMD ID' byte and availability of the respective
command:
Value
0x01
0x02
0x03
0x04
The commands 0x02 (cos phi specification), 0x03 (Q
(Q
abs
Device
Fronius IG Plus V
Fronius CL
NOTE The availability of the 0x9F command also depends on the selected
country setup of the respective inverter. To ensure that the respective inverter
supports the 0x9F command, execute the '0xBD - Get inverter capabilities'
command.
When a command is sent regarding effective power, the respective inverter continu-
es using the effective power specification last received until the next DC disconnect
in remote control mode.
When a command is sent regarding reactive power, the respective inverter continu-
es using the reactive power specification last received for 60 seconds in remote
control mode.
Command meaning
Effective power specification
Cos phi specification
Q
[%] specification
rel
Q
[VAr] specification
abs
[VAr] specification) are only available under the following conditions:
Hardware
requirement
Version 1.2A of
'PINCI 2' board
5.3.0
-
[%] specification) and 0x04
rel
Control board
software version
5.3.0
55
Required
country setup
DEMS, FR, etc.
DEMS, FR, etc.

Publicidad

loading