Descargar Imprimir esta página

CIAT MAJOR LINE Manual De Instrucciones página 36

Ocultar thumbs Ver también para MAJOR LINE:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 49
switched off.
Remove the motor/turbine assembly from the unit
To reassemble the fan motor assembly, perform these steps in reverse order.
clean them using a vacuum cleaner, taking care to ensure they are not damaged. No
special maintenance is required for the electric motor.
The condensate drain pan must be kept clean. Clean the plastic pan and its
Cleaning must be carried out with the pan removed, by unscrewing the 2 side screws
and the 2 front screws from the pan
A clean coil is crucial to the efficiency of the unit. If necessary, clean the coil
with a vacuum cleaner.
If the coil must be disassembled on account of a leak:
Disconnect the water coil and the condensate drain.
between the unit's support feet.
The condensate pan can be removed without having to remove the coil.