Power supply
230V 50Hz
1. Operating principle:
This Electronic Signal Adapter Unit works by converting a voltage-free contact signal (e.g.: from the CPFL PIR
detector) or analogicalue signal (e.g. sent by the HR% sensor) into a signal compatible with the type of actuator used
(variable voltage or frequency regulator, motor driven damper, fan motor).
2. Factory settings
-
0-20 mA analogical input (for connecting the CO2 sensor) on J3 terminal block (between GND and IN)
(switch S1.1 at ON; S1.2 and S1.3 at OFF ). Functionality used to change a signal from a single contact "unipolar"
(Input in J7) to RT contact "bipolar" (output in J1). Used for example to pilot with 2 speeds asynchronous motor by
the activation of a PIR. (An input in J7 has not action to the J4 analog output).
-
Voltage-free contact input (for connecting the presence sensor) on J7
(switch S2.1 at OFF and S2.2 at ON ).
-
0-10 V DC output (for variator and register valve control) to J4 (between GND and OUT).
-
Voltage-free rest-work contact output (for variator and multi-speed motor control) to J1.
-
Emin, Emax, Smin and Smax settings: see next paragraph.
Electronic Signal Adapter Unit
Power supply
24Vac
: suitable for most applications:
BEAS
Input relay control
simple contact
Output relay
External contact
(PIR detector)