PR electronics 7501 Manual Del Producto página 57

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK.
Explosion proof / Dust ignition proof installation:
Applicable for ( 7501A )
Explosion proof for Hazardous area
Class I, Division 1, Groups ABCD;
Class II, Division 1, Groups EFG;
Class III
Ex d IIC, Class I, Zone 1
T4,T5: -20/-40 ≤ Ta ≤ 85ºC T100°C
T6:
-20/-40 ≤ Ta ≤ 70ºC T85°C
Terminal: 3,4,5,6
Sensor: RTD or TC
O-ring Sealing
Silicone rubber:-40°C ≤Ta ≤ +85°C
FKM rubber:
Revision date:
2015-11-03
6
5
4
3
-20°C ≤Ta ≤ +85°C
Version Revision
V3R0
WWW.PRELECTRONICS.COM
+
1
-
2
7501
Supply
7501V104-ES
7501QC01
Non Hazardous Area
Terminal: 1,2
Umax: 35 VDC
Page:
2/3
57

Publicidad

Tabla de contenido
loading

Tabla de contenido