5. Installation and assembly
Pull off and remove the frame cover. Locate and fit the thermostat so that it senses the true room
temperature. Ensure that the remote sensor are not screened or hidden behind curtains or furniture
and are not exposed to draughts, direct sun light or other heat emitting appliances.
When pinning the capillary take care not to kink or flatten the tube. The surplus length of capillary
can be coiled on the frame of the thermostat (Illustration 2). Then replace the frame cover and turn
the graduated scale cap from the valve and fit the actuator. Use no excessive force or spanner.
Observe that the frame cover can be replaced in one way only, namely with the frame peg located
in the slot of the cover (Illustration 3).
Temperature limitation:
To prevent unauthorized tampering, the preset of the thermostat can be either limited or locked for
the desired temperature.
Procedure to be used for limiting the maximum room temperature:
Remove the frame cover (Illustration 4). Set the graduated scale cap to the required number.
Then remove one of the limiting pegs provided and insert it in slot behinf the graduated scale cap,
immediately to the right from the "stop rib" (Illustration 5). Finally replace the frame cover.
The procedure for limiting the minimum room temperature is similar to the one described above,
however the limiting peg must be inserted immediately to the left of the "stop rib".
Illustration 2
Illustration 4
12
Illustration 3
Illustration 5