11.3.1 Error type A or D
1
2
3
4
Fig. 40: Error type A, flowchart
1
2
3
4
5
6
8
Fig. 41: Error type D, flowchart
6.0.0.0
E000
6.0.0.0
1/1
6.0.0.0
1/1
Fig. 42: Acknowledging error type A or D
Installation and operating instructions LRE-JRE
7
60
S
0
12.3
S
Error type A (Fig. 40):
Program
Contents
step/query
1
• Error code is displayed
• Motor Off
• Red LED On
• SSM is activated
• Error meter is incremented
2
> 1 minute?
3
Error acknowledged?
4
End; auto control resumes
Yes
No
Error type D (Fig. 41):
Program
Contents
step/query
1
• Error code is displayed
• Motor Off
• Red LED On
• SSM is activated
2
• Error meter is incremented
3
Is there a new type "A" error?
4
> 1 minute?
5
Error acknowledged?
6
Is there a new type "A" error?
7
Branch to error type "A"
8
End; auto control resumes
Yes
No
If type A or D errors occur, proceed as follows to acknowledge
(Fig. 42):
• To change to menu mode, press the white button.
Menu number <6.0.0.0> flashes on the display.
• Press the white button again.
Menu number <6.0.0.0> appears steady on the display.
The time remaining until the error can be acknowledged is displayed.
• Wait until the remaining time is up.
The time until manual acknowledgement is always 60 seconds for
error types A and D.
• Press the white button again.
The error is acknowledged, and the status page is displayed.
English