8. TROUBLESHOOTING
SYMPTOM
CAUSE
Unit does
- Power cut.
not work.
- The plug has not
been plugged im-
properly.
- The full-tank indicator
is ON. Tank is full.
Unit sud-
- The indoor tempera-
denly stops
ture has reached the
during in
set temperature level.
operation.
- The preset time is up.
- The full-tank indicator
is ON. Tank is full.
Unit runs in-
- Malfunction.
termittently.
- Surrounding temper-
ature is too high or
too low.
- Exhaust duct hose is
blocked.
Unit func-
- Window or door is
tions but the
left open in the room.
room is not
- There is heat source
cooled.
in the room or too
many of people in it.
- Air intake grille is
clogged.
- Filter is too dirty.
- Temperature setting
is too high.
Condensed
- The tank is nearly full.
water is
spilled out
when mov-
ing the unit.
BEFORE CALLING FOR SERVICE
The followings are not defects.
A hissing noise or hollow
e
sound :
e
A squeaking noise :
e
Odor :
The unit does not start nor
e
change operation mode
immediately :
SOLUTION
- Wait for power to be
supplied again.
- Plug in again.
- Remove the drain
water from the drain
tank.
- Reset the tempera-
ture level.
- Reset the timer.
- Remove the drain
water from the drain
tank.
- Contact your dealer.
- Check the duct hose.
- Close all windows
and door.
- Move out any heat
source in the room.
- Clean the air intake
grille.
- Replace the filter.
- Lower the tempera-
ture setting.
- Remove the drain
plug on the rear bot-
tom of the unit, drain
off the water then the
unit will be in opera-
tion automatically.
This sound is generated from
the refrigerant flowing within
pipes.
This noise is generated from the
unit when it is expands or con-
tracts with temperature changes.
Such odor as tobacco, cosmetics,
or foods may accumulate in the
unit.
To prevent overloading the com-
pressor motor, the unit will be
stopped for more than 3 minutes.
9. SPECIFICATIONS
MODEL
COOLING CAPACITY
DEHUMIDIFYING CAPACITY
POWER SOURCE
POWER CONSUMPTION
OPERATING CURRENT
AIR FLOW (MAX.)
OPERATING TEMP. RANGE
DIMENSIONS (WxHxD)
WEIGHT
COMPRESSOR
REFRIGERANT
NOTE: Cooling air capacity will vary according to temperature
and humidity of the room.
10.VENTING KIT ACCESSORIES
If the unit is to be used exclusively in one space, the cooling ef-
ficiency will be enhanced by using the following venting kit ac-
cessories.
EXHAUST DUCT SET (FLEXIBLE TUBE) (Fig. I)
WINDOW PANEL KIT (Fig. J)
USING EXHAUST DUCT SET (Fig. I)
1.
Insert the end of exhaust duct hose (flexible tube) (I3) into
exhaust duct connector (I1) by turning it counter clockwise
onto the tube and fix it into exhaust outlet by turning it
clockwise until it locks.
2.
Insert the end of exhaust duct hose (I3) into exhaust duct
hose adapter nozzle (I2). Extend the exhaust duct hose (I3)
and close the window or door as far as possible trapping
the exhaust duct hose adapter nozzle (I2).
NOTE: Place the unit as close as possible to the window
or door.
USING WINDOW PANEL KIT (Fig. J)
NOTE: Window installations are possible by the use of
the exhaust duct set and window planel kit.
1.
Fix the exhaust duct hose grill (J3) to the window panel
with four (4) screws. Make sure that the panel is extended
so that screws do not go into sliding portion of panel.
2.
Open the window.
3.
Place the window panel in the window, extending it to fit
the width of the window. Once panel is extended, the pan-
el can be locked into this width by tightening the two (2)
screws on the top panel.
4.
Close the window.
5.
Attach the exhaust duct hose adapter nozzle (I2) on the ex-
haust duct hose grille (J3).
6.
When not in use, the exhaust duct hose adapter nozzle (I2)
may be closed off with the cover for exhaust duct hose
grille (J3) provided.
NOTE: The same procedure can be adapted for vertical
installation in sliding windows.
3
ENGLISH
TAD-30F
10,000 BTU/H
0.48 gal/h (1.8 L/H)
Single Phase 115V, 60Hz
950 W
9.0 A
188 CFM (320 m
3
/h)
64˚F~95˚F (18˚C~35˚C)
18-5/8" x 34-1/4" x 13-9/16"
(472 x 869 x 345 mm)
79 Lbs. (36 kg)
ROTARY
R-22
Max. 5 ft. (1.5m)
For sliding and double-hung
windows
Max. 37 in. (94cm)
Min. 28-1/4 in. (72cm)