Contents
­ Index ­ General warnings
Overview
Technical data
Working fields
Dimensions
Contents
Index
General warnings
Burner description
Function
General safety functions
TCG5xx control box
Terminal allocation chart 230 Volt connection
Terminal allocation chart low voltage connections
Installation
Burner assembly
Electrical connection - Checks before commissioning
Start up
Pre-setting without flame
Adjusting burner output
Setting the flame
Operating mode
Air pressure switch adjustment - setting gas pressostat - Saving the adjustment values in the display
Service
Maintenance
Troubleshooting
Troubleshooting - Fault diagnosis menu
Operating statistics menu
Overview
Gas pressure diagrams
Electrical diagrams
Spare parts list
Contents
Conformity declaration
Important notes
MAX GAS 350-500 PR burners are
designed for the low-pollutant combustion
of natural gas and Liquefied Petroleum
Gas. The design and function of the
burners comply with standard EN676.
Assembly and commissioning must be
carried out only by authorised specialists
and all applicable guidelines and directives
must be observed.
Burner description
MAX GAS 350-500 PR are two-stage
progressive, fully automatic, monoblock
type burners. The special design of the
burner head provides low-polluting
combustion with high efficiency. In line with
testing as defined by EN676, the values
comply with emissions class 3
(NOx<80mg/kWh) Emissions values may
differ, depending on combustion chamber
dimensions, combustion chamber load and
the firing system (three-pass boilers,
boilers with reverse firing).
They are suitable for use with all heat
generators complying with EN 303 or for
use with hot air generators complying with
DIN 4794, and DIN 30697 within their
respective performance range.
Ecoflam burners have been designed and built in compliance with all current regulations and directives.
All burners comply to the safety and energy saving operation regulations within the standard of their respective performance range.
The quality is guaranteed by a quality and management system certified in accordance with ISO 9001:2008.
6
www.ecoflam­burners.com
Use for any other application requires the
approval of Ecoflam.
The following standards should be
observed in order to ensure safe,
environmentally sound and
energy-efficient operation:
EN 676
Forced-draught gas burners
EN 226
Connection of fuel oil and forced-draught
gas burners to a heat generator.
EN 60335­1, ­2­102
Specification for safety of household and
similar electrical appliances, particular
requirements for gas burning appliances.
Installation location
The burner must not be operated in rooms
containing aggressive vapours (e.g. spray,
perchloroethylene, hydrocarbon
tetrachloride, solvent, etc.) or tending to
heavy dust formation or high air humidity.
Adequate ventilation must be provided at
the place of installation of the furnace
system to ensure a reliable supply with
combustion air.
Variations may arise as a result of local
regulations.
We can accept no warranty liability
whatsoever for loss, damage or injury
caused by any of the following:
- Inappropriate use.
- Incorrect assembly or repair by the
customer or any third party, including the
fitting of non-original parts.
Provision of the system and the
operating instructions
The firing system manufacturer must
supply the operator of the system with
operating and maintenance instructions on
or before final delivery. These instructions
should be displayed in a prominent
location at the point of installation of the
heat generator, and should include the
address and telephone number of the
nearest customer service centre.
Notes for the operator
The system should be inspected by a
specialist at least once a year. It is
advisable to take out a maintenance
contract to guarantee regular servicing.
420010594100
3
4
5
6
6
7
8
9-10-11
12
13
14
15
16
17-18
19-20
20
21
22-23
24
25
26
111-112
113-116
117-118
119