3-pole selective earth resistance measurement with current clamp
A
6 R
3-pole selective earth resistance
A
measurement with current clamp
Select function R
3-pole
A
Display as shown below.
Connect test leads
Connect safety test lead (1.5 m) to terminal E/C1 and its other end to the
ground system to be measured. Place 2 ground stakes. Minimum distance
between earth electrode (E/C1), probe (S/P2) and auxiliary earth (H/C2)
is 20 m!
Connect stakes with 25m and 50m wires to H/C2 and S/P2 as shown.
Connect current clamp with adapter cable as shown.
Press START
The "active" symbol indicates that measurement is in progress. For
continuous measurement keep START pressed.
Symbol "
" indicates completed measurement. The result is kept on
display until a new measurement is started or the rotary switch is turned.
1
2
max 50 V
E
S
H
plu s
3
P2
S
4
active
E
S
E
S
H
H
- 9 -