R
2-pole, 3-pole measurements
A
4 R
2-pole, 3-pole measurements
A
For 2-pole measurements connect terminals H and S with the supplied
connector cable!
Select function R
3-pole
A
Display is as shown below.
Connect test leads
Hint: Colour coded front plate and terminals provide appropriate connection.
Connect terminal E/C1 to earth electrode with short test lead (1,5 m).
Place 2 ground stakes. Minimum distance between earth electrode (E/C1),
probe (S/P2), and auxiliary earth (H/C2) is 20m!
Connect stakes with 25m and 50m wires to H/C2 and S/P2 as shown.
Press START
The "active" symbol indicates that measurement is in progress.
Continuous measurement as long as START is pressed.
Symbol "
" indicates completed measurement. The result is kept on the
display until a new measurement is started or the main switch is turned.
1
2
E
S
H
3
max 50 V
H/C2
E/C1
S/P2
easy
>20 m
>20 m
4
active
E
ES
S
H
E
ES
S
H
- 7 -