Coil ROTATION

If the bank must be turned to suit the plumbing system, proceed in the following way after having removed the front
panel (when installed):
1 . Disconnect the electricity main and make sure that no one is able to connect it again during the installation work.
2 . Remove the intake filter as illustrated in Fig.1 (version VM-B only)
3 . Remove the four screws (1-Fig.1) that fix the casing to the frame and take out the casing (version VM-B VM-F
only).
4 . Take out the following electric wiring components in sequence:
• Unscrew the ground bolt (1-Fig.2)
• Take out the terminal board (2-Fig.2)
• Take out the wire clamp (3-Fig.2)
• Take out the core hitch (4-Fig.2)
5 . Remove the screws that fix the condensation tray (5-Fig.2) and take out the tray.
6 . Remove the fixing screws from the top part of the frame (6-Fig.2) so that the side panels can be opened slightly.
7 . Remove the screws that fix the bank (7-Fig.2) and then take out this latter.
8 . Remove the pre-cuts (8-Fig.2) from the right-hand part and then close the connection through holes (of the bank
in its original configuration) on the left using adhesive anti-condensation tape.
9 . Turn the bank and fix it with the previously removed screws. Now screw on the top part of the frame.
10 .Position the condensation tray on the right-hand side, remove the right-hand drain plug spigot (9-Fig.2) and
positioning it in the left-hand one. Make sure that the plug is tight.
11 . Mount the control panel (if applicable) on the support with reference to the instructions supplied with the
accessory.
12 . Remove the plastic cover from the top left-hand side of the cabinet (version VM-B VM-F only) and fix it on the
right-hand side.
13 . Fit the casing back in place (version VM-B VM-F only)
14 . Fit the intake filter back in place (VM-B only)
15 . Hook up the electricity main again.
Fig. 2
INSTALLATION
35