1. DESCRIPTION OF THE KIT
Contents:
2. SAFETY NOTICES
ATTENTION!
Disconnect the supply of the Soft-Starter SSW-07/SSW-08 before installing
the Enclosure Size 3 Ventilation Kit. The electronic boards have components
that are susceptible to electrostatic discharge. Never touch any of the
electrical components or connectors without following the proper grounding
procedures. If it is necessary to do so, touch the grounded heatsink or use
a suitable grounded wrist strap.
3. OPTIONAL MODULE DESCRIPTION
This module improves the thermal capacity of the Soft-Starter.
The Enclosure Size 3 Ventilation kit is connected directly to the SSW-07/SSW-08. The
module is fixed at the bottom of the Soft-Starter, at the heatsink.
NOTE!
This kit is necessary for a regimen of more than 3 starts per hour (every 20
minutes) at the following conditions: 3 x In during 30 s (SSW-07) or 3 x In during
20 s (SSW-08) with an ambient temperature of 55 °C, (131 °F).
NOTE!
The fans are activated only with high heatsink temperature and during the
acceleration or deceleration ramp.
2
Table 1 - Contents of the Kit
SSW-07/SSW-08 Enclosure Size 3 Ventilation Kit (Part number: 10413865)
Quantity
1
SSW-07/SSW-08 enclosure size 3 optional ventilation kit
Description