EMKO RS Pro ESM-3711-CN Manual De Instrucciones página 10

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Defrost Delay at Power On Parameter
It can be adjusted from 0 to 99 minutes. This parameter can be observed if defrost at power
on parameter
is 1.
Display Status During Defrost Parameter
The temperature is displayed during defrost.
Temperature value at the start of a defrost is displayed during defrost.
Set value is displayed during defrost.
Is displayed to indicate a defrost is in progress.
Compressor Start Delay at Power On Parameter ( Default = 0)
MODBUS ADDRESS:40014
When power is first applied to the device, compressor is on when this time delay is expired.
It can be adjusted from 0 to 20 minutes.
Compressor Stop-Start Delay Parameter ( Default = 0) MODBUS ADRES:40015
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Compressor Start-Start Delay Parameter
This time delay must be expired between two activation of the compressor. It can be
adjusted from 0 to 20 minutes.
Sensor Defect Parameter ( Default = 0 ) MODBUS ADRES:40017
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to
case of sensor defect.
Compressor is active during this time period in case of probe defect (Default = 0)
MODBUS ADRES:40018
If probe defect parameter
from 0 to 99 minutes.
Compressor is inactive during this time period in case of probe defect
( Default = 0 )MODBUS ADRES:40019
If probe defect parameter
from 0 to 99 minutes.
Temperature Alarm Function Selection Parameter
MODBUS ADRES:40020
Alarm function is inactive.
Absolute alarm is selected. If temperature lower than
than
, then alarm is on.
Relative alarm is selected. Alarm operates according to the set value.
If temperature is below ( Set -
Temperature Minimum Alarm Parameter (Default =Minimum Value of Device Scale)
MODBUS ADRES:40021
For temperature alarm function selection parameter
parameter value is can be adjust from minimum value of device scale to temperature
alarm maximum parameter
parameter
= 2(Relative alarm), this parameter value is can be adjusted 0 to %50 of
the device scale
Temperature Alarm Maximum Parameter
MODBUS ADRES:40022
For temperature alarm function selection parameter
parameter value is can be adjust from temperature alarm minimum parameter
value to maximum value of device scale, for temperature alarm function selection
parameter
= 2(Relative alarm), this parameter value is can be adjusted 0 to %50
of the device scale
( Default = 0) MODBUS ADDRESS:40012
( Default = 3 ) MODBUS ADDRESS:40013
( Default = 0) MODBUS ADRES:40016
is 2, then this parameter is observed. It can be adjusted
is 2, then this parameter is observed. It can be adjusted
( Default = 0 )
) or above ( Set +
value , for temperature alarm function selection
( Default = Maximum Value of Device Scale)
and
Time periods in
and higher
), alarm occurs.
= 1(Absolute alarm), this
= 1(Absolute alarm), this
10

Publicidad

Tabla de contenido
loading

Tabla de contenido