Temperature Alarm On Delay Time Parameter(Default = 0)MODBUS ADDRESS:40023
Temperature alarm on delay time can be defined with this parameter.
It can be adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
MODBUS ADRES:40024
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm. It can be adjusted from 0 to 99 minutes.
Buzzer Function Selection Parameter
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs.
Buzzer is active during sensor failures.
Buzzer is active during defrost operation, alarm or sensor failures.
Buzzer is active during this time
If buzzer function selection parameter value
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
When this parameter is 1, if decrement button is pressed,
condition buzzer is active till buzzer silence button is pressed.
Button Protection Parameter
There is no protection.
Defrost time can not be changed and manual defrost is not available.
Temperature Set value can not be changed.
Defrost time set value and temperature set value can not be changed. Manual
defrost is not available.
Defrost time value can not be changed, manual defrost is available..
Communication Mode Selection Parameter
PROKEY communication selected.
Rs485 communication selected.
Slave ID Parameter
( Default = 1 ) MODBUS ADDRESS=40029
Device communication address parameter (1 to 247).
ON/OFF Parameter
( Default = 0 ) MODBUS ADDRESS:40030
When device energized; if
controlling and
screen will be displayed. If
10 seconds, device continues controlling and display changes back to main operating
screen.
ON/OFF function with
ON/OFF function with
Programming Section Accessing Password
It is used for accessing to the programming section. It can be adjusted from 0 to 999. If it is
selected 0, password will not be asked
parameters will be accessible.
( Default = 0 ) MODBUS ADDRESS:40025
( Default =
=0, this parameter can not be
( Default = 4 ) MODBUS ADDRESS:40027
( Default = 0 ) MODBUS ADDRESS:40028
(increment button) pressed for 10 seconds, device stops
(increment button) pressed again for
button is not available.
button is available.
( Default = 0 ) MODBUS ADDRESS:40031
. If password selected '12', only
( Default = 0 )
) MODBUS ADDRESS:40026
is observed. In this
,
and
11