4.4.3 - Power supply
• 230V / 1 + Earth / 50Hz power supply from a power supply and protection device (not included) in accordance
with the rules in force. The protection must be ensured by a two-pole circuit breaker (not supplied).
Note: The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or
TN.S regime (to neutral) as per NF C 15-100.
GB
For a IT neutral point connection (isolated neutral), provide ground fault protection.
• The acceptable voltage variation is ± 10% during operation.
• Wire sizes are given for informational purposes only. Wire sizes must be checked and adapted, as required,
according to the installation conditions and with regard to current standards.
Models
Max. current consumption (A)
Section (mm
2
)
ELECTRIC WIRING DIAGRAMS
4.5 -
Symbols of components
C1
Condenser
FLP Flap motor
FMI
Indoor fan motor
PCB Controller
TH1,2 Thermistor
RMV Fan motor relay
R1
Heater
CWX3-5 MODELS
WITH VALVE CONTROL (ON/OFF)
8
CWX 3
CWX 5
0,25
0,40
1,5
1,5
Models
Max. current consumption (A)
Section (mm
2
)
Colours of the wires
WHT
White
BLK
Black
GRY
Grey
RED
Red
YEL
Yellow
BRN
Brown
VLT
Violet
ORG
Orange
PNK
Pink
BLU
Blue
GRN/YEL
Yellow/Green
CWX 6/8
CWX 10
0.65
0.95
1.5
1.5