4. TECHNICAL DATA:
AC Input Power
Settings
Diagnostics
Start Duty
Digital Inputs
(90...250Vac 6mA)
Relay
Outputs (1A 250Vac)
Communication
Ambient
Degree of Protection
Polution Degree (UL508)
Mounting
Electromagnetic Compatibility
Standards
Model
Control Voltage (A1 and A2)
Power supply
(R/1L1, S/3L2, T/5L3)
Pedestal Voltage
Acceleration Time
Deceleration Time
Motor Current
Maximum Number of Starts
per hour
Starting Cycle
Temperature
Humidity
Altitude
Fastening
Enclosure
(EMC)
Low Voltage
English-4
SSW-05 Plus
90 ... 250Vac 50/60 Hz (+/- 6Hz)
200 mA
220 ...460 Vac (+10%,-15%) 50/60 Hz (+/- 5Hz) 3φ
460 ... 575 Vac (+10%,-15%) 50/60 Hz (+/- 5Hz) 3φ
30 ... 80% U
1 ... 20 s
Off ... 20 s
30 ... 100% I
Motor Overload Protection
Incorrect Phase Sequence
Phase Loss
Immediate Overcurrent
Locked Rotor
Thyristor Overload
Immediate Overload at
By-pass Relay
Overcurrent before By-pass
Frequency out of Tolerance
Internal By-pass Relay
Contact is open
Undervoltage at control
voltage
4 ( 1 start every 15 minutes)
3 x I
during 10 seconds
N
DI1 – Enable/Disable Function
DI2 – Reset Function
Operation Function (13 – 14/23)
Full Voltage Function (14/23 – 24)
Serial Interface (RS232C)
0 ... 55°C (32...131°F)
5 ... 90% Non Condensing
0 ... 1000m (up to 13,200 ft (4000m) with
10% output current derating/1000m)
IP 00 (Chassis)
2
DIN 35mm rail or M4 fastening bolts
Molded plastic box
Class A (industrial use)
IEC 60947-4-2 Standard
UL 508 / IEC 60947-4-2
N
N