Quick Parameter Reference, Faults and Alarms
Fault/Alarm
F0006:
The mains voltage imbalance is too
Input Voltage
high or phase loss at the supply line
Imbalance or Phase
has occurred.
Note:
Loss
- This fault may not occur if the
load at the motor shaft is too low or
nonexistent.
P0357 sets the time for the trip, and
P0357 = 0 disables this fault.
F0021:
A DC link undervoltage condition has
DC Link
occurred.
Undervoltage
F0022:
A DC link overvoltage condition has
DC Link Overvoltage
occurred.
A0046:
It is the motor overload alarm.
Note:
High Load at the
Motor
It can be disabled by setting
P0348 = 0 or 2.
A0047:
It is the IGBT overload alarm.
IGBT Overload
Note:
Alarm
It can be disabled by setting
P0350 = 0 or 2.
F0048:
It is the IGBT overload fault.
IGBT Overload Fault
A0050:
The NTC temperature sensors
IGBT High
located in the IGBTs detected a high
Temperature
temperature alarm.
Note:
It can be disabled by setting
P0353 = 2 or 3.
F0051:
The NTC temperature sensors
IGBT
located in the IGBTs detected a high
Overtemperature
temperature fault.
F0070:
An overcurrent or a short-circuit at
Overcurrent/
the output, at the DC link or at the
Short-circuit
braking resistor, has occurred.
F0071:
An output overcurrent has occurred.
Output Overcurrent
22 | CFW701
Description
Possible Causes
A Phase Loss at the inverter input.
The input voltage imbalance is > 5 %.
The input voltage is too low and the DC link voltage
dropped below the minimum permitted value (monitor
the P0004 parameter value):
Ud < 223 V - 200 / 240 V three-phase input voltage;
Ud < 170 V - 200 / 240 V single-phase input voltage
(CFW701XXXXS2 or CFW701XXXXB2 models)
(P0296 = 0);
Ud < 385 V - 380 V input voltage (P0296 = 1);
Ud < 405 V - 400 / 415 V input voltage (P0296 = 2);
Ud < 446 V - 440 / 460 V input voltage (P0296 = 3);
Ud < 487 V - 480 V input voltage (P0296 = 4);
Ud < 530 V - input voltage 500 / 525 V (P0296 = 5);
Ud < 580 V - input voltage 550 / 575 V (P0296 = 6);
Ud < 605 V - input voltage 600 V (P0296 = 7).
Phase loss at the inverter input.
Pre-charge circuit failure.
Parameter P0296 was set to a value higher than the
power supply rated voltage.
Too high input voltage, resulting in a DC link voltage
higher than the maximum permitted value:
Ud > 400 V - 220 / 230 V models (P0296 = 0);
Ud > 800 V - 380 / 480 V models (P0296 = 1, 2, 3, or 4);
Ud > 1000 V - 500 / 600 V models (P0296 = 5, 6 or 7).
The inertia of the driven-load is too high or the
deceleration time is too short.
The parameter P0151, P0153 or P0185 setting is
too high.
The settings of P0156, P0157 and P0158 are too low
for the used motor.
There is excessive load at the motor shaft.
The inverter output current is too high.
The inverter output current is too high.
High surrounding air temperature (>50 °C (122 °F))
and high output current.
Blocked or defective fan.
Very dirty heatsink.
Short-circuit between two motor phases.
Short-circuit between the dynamic braking resistor
connection cables.
Shorted IGBT modules.
Excessive load inertia or too short acceleration ramp.
P0135, or P0169 and P0170 settings are too high.