Troubleshooting
Flashes
Controller Status
8 Blinks
Over Voltage
9 Blinks
Motor Overload
Red Light Codes (continued)
Description
This fault can be caused by:
• High input voltage.
This fault will be displayed if the phase to phase input voltage is
greater than 275V for 230V units and 560V for 460V units.
This fault can be caused by:
• Mechanical binding from debris in pump.
• Electrical failure of the motor.
• Incorrect setting of Motor Overload Setting switches.
• Incorrect rotation.
The controller will protect the motor from over current by limiting the
current applied to the motor. The current limit is set according to the
Motor Overload Setting switches. This fault is displayed if the output
frequency is reduced to limit the current to the motor by more than
10Hz for 5 minutes.
24