EdilKamin DOUBLE Manual De Instalación, Uso Y Manutención página 18

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32
INSTALLATION INSTRUCTIONS
Building protection
All the building surfaces near the hearth
must be protected against heat. The type
of insulation to be adopted depends on the
type of surfaces present and how they are
made.
Hot air outlets / Grills
The hot air outlets must be placed at a
minimum distance of 50 cm from the
ceiling and 30 cm from the furniture.
Position the grills or the air outlets at the
highest point of the covering, in order to
avoid heat accumulating inside the same
covering. Position the grills or the air outlets
so that they can be easily accessed for
cleaning.
Heating insulation
The insulating layers must not have joints
and have to be overlapped. The thickness
of the insulating material must be of at least
3 cm.
Ornamental beams
The realisation of eventual wood
ornamental beams in front of the hearth
covering is allowed only if they are outside
the radiation field, at a distance of at least
1 cm from the same covering. The air space
between the ornamental elements and the
covering must be such not to accumulate
heat.
The wood ornamental beams cannot be
integrating parts of the building.
Floor opposite the hearth
The floors built with fuelling materials
must be protected by sufficiently thick, non
fuelling cover, or must be replaced with a
non fuelling floor. The floor protection must
be equal to:
frontally:
- the corresponding height of the fire
surface from the floor plus 30 cm and, in
any case, min. 50 cm
laterally:
- the corresponding height of the fire
surface from the floor plus 20 cm and, in
any case, min. 30 cm.
18
In the radiation fi eld of the
hearth
The structural elements built with fuelling
material or which present fuelling
components and the furniture must be
positioned at a minimum distance of 80
cm from the hearths mouth, in all three
directions: front, upper and side. Whenever
such elements or furniture were screened by
a ventilated anti-radiation protection, it will
be sufficient to respect a distance of 40 cm.
Outside the radiation fi eld
The structural elements built with fuelling
materials or which present fuelling
components and the furniture, must be
positioned at a minimum distance of 5
cm from the hearths covering. In such
air space, the air present in the room
must be able to circulate freely. No heat
accumulation must be created.
Electric lines
There must be no electric lines in the walls
and the ceilings, including the hearth
embedding area.

Publicidad

Tabla de contenido
loading

Tabla de contenido