STATIC PROTECTION KIT

GROUND WIRE ASSEMBLY
CLAMPED TO EARTH
GROUND
GROUND
WIRE (NOT
INCLUDED)
EARTH GROUND
DRUM PUMP
DRUM PUMP INSTALLATION
1. Install the pump and Static Protection Kit as described and
shown.
2. Connect ground wire assembly to earth ground using sup-
plied clamp.
3. Connect ground wire between drum and earth ground.
4. Connect ground wire between receiving container and earth
ground (or use bonding wire to connect to drum).
CAUTION - Check electrical continuity of all components
before pumping. All should be one (1) ohm or less.
TUBE MIXER INSTALLATION
1. Install the mixer and Static Protection Kit as described and
shown.
2. Connect ground wire assembly to earth ground using sup-
plied clamp.
3. Connect ground wire between drum and earth ground.
CAUTION - Check electrical continuity of all components
before pumping. All should be one (1) ohm or less.
EXPLOSION PROOF OR
AIR MOTOR
GROUNDED HOSE
WITH GROUND WIRE
ASSEMBLY
BONDING
WIRE (NOT
PROVIDED)
NO
SPLASHING
16 16
GROUND WIRE ASSEMBLY
CLAMPED TO EARTH
GROUND
GROUND WIRE
WITH PIPE
CLAMP (NOT
INCLUDED)
OPERATION AND SAFETY GUIDELINES
• Use only metallic pump tubes with explosionproof motors to
transfer flammable or combustible liquids.
• Area for use must comply with NFPA 30 guidelines for safe
storage and use of flammable and combustible liquids.
• All containers and other equipment must be metal and
grounded.
• Follow NFPA 77 guidelines for control of static electricity.
• Avoid splashing. Splash filling can create static electricity
and is extrememly hazardous.
• Fluid velocity must be 3 feet/second maximum (7 GPM in
1" hose).
EXPLOSION PROOF OR
AIR MOTOR
EARTH GROUND
MIXER