OPERaTING TEST
using the remote controls
Obstacle detection operation
When an obstacle is detected during closing, the door re-opens (Fig. 17).
When an obstacle is detected during opening, the door will stop (Fig. 18).
Check that the obstacle detection function works when the door encounters a 50 mm high obstacle on the ground.
Integrated lighting operation
The lighting comes on each time the motorisation is switched on. When the door stops moving, it goes off automatically after 30 seconds. Repetitive
use will cause the light to be lit constantly which may result in the light being switched off automatically due to thermal protection.
CONNECTING aDDITIONal DEvICES
Description of the various additional devices
No.
Description
1
Orange light
2
Wired code keypad
3
Key lock
4
Aerial
5
Battery
6
Photoelectric cells
Electrically connecting additional devices
Switch off the electrical supply to the motor before performing any operation on the additional devices.
General electrical diagram (fig. 19)
Photoelectric cells (fig. 20)
When positioning the cells, remove the bridge created between terminals 1 and 2.
If cells are removed, it is essential to recreate the bridge between terminals 1 and 2.
Solar kit (fig. 21)
Activate solar mode by adjusting the motor supply type (see below).
Wired code keypad (fig. 22)
PaRamETER SETTING aND OPERaTING OPTIONS
General parameter-setting diagram
meaning of different parameters
Programming example: Adjusting the long slow zone (Fig. 24)
Warning light a
Description
Obstacle detection
sensitivity
Coupling speed when
closing
Auto-programming mode
Power supply type
SPIDER PRO 600
fig. 16
fig. 17 and 18
fig. 19
fig. 19 to 22
fig. 23
Warning light B
1
: very low sensitivity
2
: slightly sensitive
3
: standard
4
: very sensitive
1
: no reduction in speed
2
: short reduction in speed
3
: long reduction in speed
2
: waiting for auto-programming
1
: Power supply
2
: Solar
automatismos pujol -
https://appceso.com
Comments
If this parameter is modified, it is essential to perform the
force measuring procedure at the end of the installation
operation.
No reduction in speed at the end of closing.
The speed is reduced during the last 30 centimetres.
The speed is reduced during the last 50 centimetres.
If this parameter is modified, it is essential to perform the force
measuring procedure at the end of the installation operation.
6
- english