Mitsubishi Electric MXZ-3B24NA Manual De Instalación página 6

Ocultar thumbs Ver también para MXZ-3B24NA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3=1. FLARING WORK
1) Cut the copper pipe correctly with pipe cutter. (Fig. t, 2)
2) Completely
remove all burrs from the cut cross section
of pipe. (Fig. 3)
• Aim the copper pipe downward
while removing
burrs
to prevent burrs from dropping
in the pipe.
3) Remove flare nuts attached to indoor and outdoor units,
then put them on pipe having
completed
burr removal.
(Not possible to put them on after flaring work.)
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the
dimension
shown
in the table. Select
A mm from the
table according to the tool selected.
5) Check
• Compare the flared work with Fig. 6.
• If flare is noted to be defective,
cut off the flared sec-
tion and do flaring work again.
Fig. t
Flaring tool
Clutch type
Wing nut type
Fig. 4
Good
No good
Tilted Uneven Burred
Fig. 2
A
Die -J_-
Copper pipe
/
Flare nut
Fig. 5
urr
C_:C_s; aPleP e.....
I_
_,,_.Pipe
cutter
I_ _
Fig.
3
Inside is shin-
Smooth al!
ing without any
.....
d z,_¢
\ .... tches.
_-.i_ Even length
all around
i
Fig. 6
II
Pipe diameter
Nut
[mm (inch)]
(mm)
e6.35 (t/4)
t7
e9.52 (3/8)
22
et2.7
(t/2)
26
et5.88
(5/8)
29
j Clutch type tool for R410A
0 to 0.5
(0 to 0.02)
A [mm (inch)]
Clutch type tool for R22
1.0 to t .5
(0.04 to 0.06)
Wing nut type tool for R22
N.m
1.5 to 2.0
t3.7 to 17.7
(0.06 to 0.08)
34.3 to 41.2
2.0 to 2.5
49.0 to 56.4
(0.08 to 1.0)
73.5 to 78.4
Tightening
torque
kgf-cm
140 to t80
350 to 420
500 to 575
750 to 800
ftolb
t0 to t3
25 to 30
36 to 42
54 to 58
3=2. PiPE CONNECTION
1) Apply a thin coat of refrigeration
oil (G) to the flared ends of the pipes and
the pipe connections
of the outdoor unit.
2) Align the center of the pipe with that of the pipe connections
of the outdoor
unit, then hand tighten the flare nut 3 to 4 turns.
3) Tighten the flare nut with a torque wrench as specified
in the table.
• Over-tightening
may cause damage to the flare nut, resulting
in refriger-
ant leakage.
• Be sure to wrap insulation around the piping. Direct contact with the bare
piping may result in burns or frostbite.
3=3. iNSULATiON AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including
valves.
3) Using piping tape (E), apply taping starting from the entry of outdoor unit.
• Stop the end of piping tape (E) with tape (with adhesive agent attached).
• When piping have to be arranged
through above ceiling, closet or where
the temperature
and humidity are high, wind additional
commercially
sold
insulation to prevent condensation.
4=1. PURGING PROCEDURES AND LEAK TEST
1) Remove service port cap of stop valve on the side of the outdoor unit gas
pipe. (The stop valves are fully closed and covered
in caps in their initial
state.)
2) Connect
gauge manifold
valve and vacuum pump to service port of stop
valve on the gas pipe side of the outdoor unit.
3) Run the vacuum pump. (Vacuumize
for more than t5 minutes.)
4) Check the vacuum with gauge
manifold
valve, then close gauge manifold
valve, and stop the vacuum pump.
5) Leave as it is for one or two minutes.
Make sure the pointer
of gauge
manifold valve remains
in the same position. Confirm that pressure
gauge
shows
0.101 MPa [Gauge] (-760 mmHg) (-30 in. Hg).
6) Remove gauge manifold valve quickly from service port of stop valve.
7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating
without fully opening lowers the performance
and this causes trouble.
8) Refer to t-2.
and charge the prescribed
amount of refrigerant
if needed.
Be sure to charge slowly with liquid refrigerant.
Otherwise,
composition
of
the refrigerant
in the system may be changed
and affect performance
of
the air conditioner.
9) Tighten cap of service port to obtain the initial status.
10)Leak test
0.101MPa
[-760 mmHg
Compound pressure
*4 to 5 turns
Stop valve cap
(-30 in. Hg)]
gauge (for R410A)
(Torque 19.6 to 29.4 Nora,
Pressure gauge
*Close
200 to 300 kgfocm,15 to
R410A)
*Ope
22 ft.lb)
e manifold
"_-
Stop valve
valve(for R410A)
_L_
for GAS
Handle High
Hexagonal wrench
Low
e hose
(for R410A)
Service
port
(Torque
13.7 to
17.7 N,m, 140 to
180 kgfocm, 10 to
13 ffolb)
,-Stop valve
for LIQUID
Vacuum
pump
(for R410A)
Precautions
when using
When attachinq the control valve to
the contro
va ve
the service port valve core may de-
form or loosen if excess pressure is
---',,]V_'_
U
applied. This may cause qas leak.
CentreA
valve ---"_ II::_:_q_&_:d
Ope.--_
i ._Service
port
When attaching
the control valve to
CIose_"€_ _'_-Ld_'=_m-
'_- _'_/
the service port, make sure that the
valve core is in closed position, and
......
then tighten part A. Do not tighten
t
Charge hose part A or turn the body when valve
Body
(for R410A)
core is in open position.
En-5

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mxz-3b30naMxz-4b36na

Tabla de contenido