salmson SIRIUX O home Instalacion Y Puesta En Servicio página 31

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Salmson
The following table shows the recommended minimum flow per
line relative to the pipe diameter, in order to ensure a flow rate of
0.2 m/s per line:
Inner pipe diameter
[mm]
14
16
20
26
33
40
In order to set the minimum flow on the pump, the number of
ascending lines must be multiplied by the "minimum flow per
line. Recommendations could vary from country to country.
Please conform to local ones.
5.2 Activating thermal disinfection
• Use the white operating knob (8) to select the "Thermal
disinfection" menu and then select ON.
-> The display (7) shows on in the icon and also dsft.
NOTE: Thermal disinfection takes precedence over the operating
mode.
5.3 Activating key lock
• Use the white operating knob (8) to select the "Thermal
disinfection" menu.
• Press the red operating knob (8) for 10 seconds.
-> The display (7) shows Hold and OFF alternately.
• Select the ON setting.
• Press the red operating knob.
-> The key lock is activated. Settings cannot be changed and
the pump and power consumption meter cannot be reset.
NOTE: The key lock does not activate automatically and cannot
be deactivated by switching off the pump.
Minimum flow per line
[m³/h]
0,11
0,14
0,23
0,38
0,62
0,90
English
31

Publicidad

Tabla de contenido
loading

Tabla de contenido