Installation and maintenance manual
5.1.1.7
Restoring default factory settings
To carry out the procedure:
Ensure that the keyboard is not locked
(paragraph Errore. L'origine riferimento non è
stata trovata.) and that no other advanced
procedure is in progress;
Keep the
and the
seconds: the display will show "PA" (password);
Press and release the
Press and release either the
within 15 seconds to set "149";
Press and release the
out any operations for 15 seconds;
Keep the
and the
seconds: the display will show "dEF";
Press and release the
Press and release either the
within 15 seconds to set "1";
Press and release the
out any other operations for 15 seconds: the
display will show "dEF" flashing for 4 seconds,
after which the equipment will exit the
procedure;
Disconnect the equipment from the mains
power supply.
To exit the procedure before its completion:
Keep the
and the
seconds during the procedure (or rather
before setting "1": the restoring of default
factory settings will not be carried out).
5.1.1.8
TOTAL OF THE COMPRESSOR
OPERATING HOURS
5.1.1.8.1
General information
The equipment is capable of memorising up to
9,999 compressor operating hours, if the number of
hours exceeds "9,999" it flashes
keys pressed for 4
key;
or the
key
key or do not carry
pressed for 4
key;
or the
key or do not carry
key pressed for 4
.
5.1.1.8.2
Display of compressor operating hours
Make sure that the keyboard is not locked
(paragraph Errore. L'origine riferimento non è
stata trovata.) and that no other advanced
procedure is in progress;
Press and release the
show "Pb1";
Press and release either the
to select "CH";
Press and release the
To exit the procedure:
Press and release the
out any other operation for 60 seconds.
Alternatively:
Press and release the
5.1
Particular operations
The product has a fan speed control system that
increases the speed of the same, when the
ambient temperature drops to below -1°C, at
higher temperatures, the fan maintains a lower
speed in order to reducing the noise of the
equipment.
The equipment is also provided with a verification
system of the environmental conditions concerning
the temperatures of the external incoming air. The
below described function is necessary to avoid the
equipment working with the heat pump mode out
of specification, which may cause faults to the
compressor and the consequent interruption of the
functionality.
By every start, the fan is activated for a time set up
by parameter C12 corresponding to 1 minute.
After this time, the system measures the incoming
air temperature. If the temperature is equal to or
lower than parameter SP9 (-7°C), then the
conditions for the activation of the heat pump unit
are not met, therefore the electric resistance is
activated. The heating-up process continues with
the help of the electrical resistance until the set
point established with the ongoing active cycle is
reached.
The system verifies cyclically (every 120 minutes)
the environmental conditions and activates the
heat pump mode only when this conditions are
adequate for its operation.
key: the display will
or the
key
key.
key or do not carry
key.
pag. 17 / 23